Product Data Sheet   5292

HBL5292I

Ivory nylon face, 2 circuit, back and side wired.

Hubbell Wiring Device-Kellems Product Specifications
 Device Type  Combination Face Duplex Receptacle
 Hospital Grade ?  No
 Receptacle Grade  Heavy Duty Spec Grade
 Face Style  Finder Groove
 Face A  6-15R
 Face B  5-15R
 Wiring Style  2 Circuit
 Color  
 NEMA No.  5-15R, 6-15R
 Horsepower  1.5 Max.
 Combo Wiring Method  Back and Side
 Description  Heavy Duty Combo Duplex Receptacle
 Type  2 Pole, 3 Wire, Grounding
 Rating  15A, 125V/15A, 250V
 Certification  UL Listed, File E2186, Guide RTRT Fed Spec WC596G, Meets NEMA WD-6 requirements Listed to UL Standard 498, Certified to CSA, C22.2, No. 42 where applicable
 Terminal Screw Material  #8-32 Brass, Multiple Drive
 Ground Screw Material  #8-32 Brass, Multiple Drive (Green)
 Wire Clamps Material  0.062" (1.6) Steel - Ni Plated
 Top Material  Nylon
 Base Material  Reinforced PET
 Power Contacts Material  .037" (.9) Brass
 Mounting Strap Material  .050" (1.3) Brass
 Center Assembly Rivet Material  Brass
 Auto Ground Clip Material  Stainless Steel
 Mounting Screw Material  Steel-Zinc Plated
 Dielectric Voltage  Withstands 2,000V minimum.
 Current Interrupting  Certified for current interrupting at full rated current.
 Temperature Rise  Max 30°C temperature rise at full rated current after 50 cycles of overload at 150% of rated current at a power factor of 75%..
 Terminal Identification  Terminals identified in accordance with UL498 (Brass, White, Green).
 Terminal Accommodation  #14-#10 AWG copper stranded or solid conductor only.
 Product Identification  Ratings are a permanent part of the device..
 Flammability  Top: UL 94 V2. Base: UL 94 V0 and UL 94-5 VA.
 Operating Temperatures  Maximum continuous 75°C, minimum -40°C (w/o impact).




 

Hubbell Wiring Device-Kellems